Subpart N--National Emission Standards
for Chromium Emissions from Hard and Decorative Chromium Electroplating
and Chromium Anodizing Tanks
63.340 Applicability and
designation of sources.
63.341 Definitions and nomenclature.
63.342 Standards.
63.343 Compliance provisions.
63.344 Performance test requirements and test
methods.
63.345 Provisions for new and reconstructed sources.
63.346 Recordkeeping requirements.
63.347 Reporting requirements.
For the reasons set out in the preamble, title 40, Chapter I
of the Code of Federal Regulations is amended as set forth below.
PART 9-[AMENDED]
1. The authority citation for part 9 continues to read as follows:
Authority: 7 U.S.C. 135 et seq., 1235136y; 15 U.S.C. 2001,
2003, 2005, 2006, 2601-2671; 21 U.S.C. 331j, 346a, 348; 31 U.S.C.
9701; 33 U.S.C. 1251 et seq., 1311, 1313d, 1314, 1321, 1326, 1330, 1344,
1345(d) and (e), 1361; E.O. 11735, 38 FR 21243, 3 CFR, 1971-1975;
Comp. p. 973; 42 U.S.C. 241, 242b, 243, 246, 300f, 300g, 300g1,
300g2, 300g3, 300g4, 300g5, 300g6, 300j1,
300j2, 300j3, 300j4, 300j9, 1857 et seq., 69016992k,
74017671q, 7542, 96019657, 11023, 11048.
2. Section 9.1 is amended by adding a new entry to the table under
the indicated heading to read as follows:
§ 9.1 OMB approvals under the Paperwork Reduction Act.
PART 63-[AMENDED]
1. The authority citation for part 63 continues to read as follows:
Authority: 42 U.S.C. 7401 et seq.
2. By adding a new subpart N to read as follows: Subpart N--National
Emission Standards for Chromium Emissions from Hard and Decorative
Chromium Electroplating and Chromium Anodizing Tanks Sec.
Subpart N--National Emission Standards for Chromium Emissions
from Hard and Decorative Chromium Electroplating and Chromium Anodizing
Tanks
§ 63.340 Applicability
and designation of sources.
(a) The affected source to which the provisions
of this subpart apply is each chromium electroplating or chromium
anodizing tank at facilities performing hard chromium electroplating,
decorative chromium electroplating, or chromium anodizing.
(b) Owners or operators of affected sources
subject to the provisions of this subpart must also comply with the
requirements of subpart A of this part, according to the applicability
of subpart A to such sources, as identified in Table 1.
(c) Process tanks associated with a chromium
electroplating or chromium anodizing process, but in which neither
chromium electroplating nor chromium anodizing is taking place, are
not subject to the provisions of this subpart. Examples of such tanks
include, but are not limited to, rinse tanks, etching tanks, and
cleaning tanks. Likewise, tanks that contain a chromium solution,
but in which no electrolytic process occurs, are not subject to this
subpart. An example of such a tank is a chrome conversion coating
tank where no electrical current is applied.
(d) Affected sources in which research and
laboratory operations are performed are exempt from the provisions
of this subpart when such operations are taking place.
(e) The owner or operator of an affected
source subject to the requirements of this subpart is required to
obtain a title V permit from the permitting authority in which the
affected source is located.
§ 63.341 Definitions
and nomenclature.
(a) Definitions. Terms used in this
subpart are defined in the Act, in subpart A of part 63,
or in this section. For the purposes of subpart N, if the same term
is defined in subpart A and in this section, it shall have the meaning
given in this section.
Add-on air pollution control device means
equipment installed in the ventilation system of chromium electroplating
and anodizing tanks for the purposes of collecting and containing
chromium emissions from the tank(s).
Air pollution control technique means
any method, such as an add-on air pollution control device or a chemical
fume suppressant, that is used to reduce chromium emissions from
chromium electroplating and chromium anodizing tanks.
Base metal means the metal or metal
alloy that comprises the workpiece.
Bath component means the trade or
brand name of each component(s) in trivalent chromium plating baths.
For trivalent chromium baths, the bath composition is proprietary
in most cases. Therefore, the trade or brand name for each component(s)
can be used; however, the chemical name of the wetting agent contained
in that component must be identified.
Chemical fume suppressant means any
chemical agent that reduces or suppresses fumes or mists at the surface
of an electroplating or anodizing bath; another term for fume suppressant
is mist suppressant.
Chromic acid means the common name
for chromium anhydride (CrO3).
Chromium anodizing means the electrolytic
process by which an oxide layer is produced on the surface of a base
metal for functional purposes (e.g., corrosion resistance or electrical
insulation) using a chromic acid solution. In chromium anodizing,
the part to be anodized acts as the anode in the electrical circuit,
and the chromic acid solution, with a concentration typically ranging
from 50 to 100 grams per liter (g/L), serves as the electrolyte.
Chromium electroplating or chromium anodizing
tank means the receptacle or container in which hard or decorative
chromium electroplating or chromium anodizing occurs.
Composite meshpad system means
an add-on air pollution control device typically consisting of several
meshpad stages. The purpose of the first stage is to remove
large particles. Smaller particles are removed in the second stage,
which consists of the composite mesh pad. A final stage may remove
any reentrained particles not collected by the composite mesh pad.
Decorative chromium electroplating means
the process by which a thin layer of chromium (typically 0.003 to
2.5 microns) is electrodeposited on a base metal, plastic, or
undercoating to provide a bright surface with wear and tarnish resistance.
In this process, the part(s) serves as the cathode in the electrolytic
cell and the solution serves as the electrolyte. Typical current
density applied during this process ranges from 540 to 2,400 Amperes
per square meter (A/m2) for total plating times ranging
between 0.5 to 5 minutes.
Electroplating or anodizing bath means
the electrolytic solution used as the conducting medium in which
the flow of current is accompanied by movement of metal ions for
the purposes of electroplating metal out of the solution onto a workpiece
or for oxidizing the base material.
Emission limitation means, for the
purposes of this subpart, the concentration of total chromium allowed
to be emitted expressed in milligrams per dry standard cubic meter
(mg/dscm), or the allowable surface tension expressed in dynes per
centimeter (dynes/cm).
Facility means the major or area source
at which chromium electroplating or chromium anodizing is performed.
Fiber-bed mist eliminator means an
add-on air pollution control device that removes contaminants from
a gas stream through the mechanisms of inertial impaction and Brownian
diffusion. These devices are typically installed downstream of another
control device, which serves to prevent plugging, and consist of
one or more fiber beds. Each bed consists of a hollow cylinder formed
from two concentric screens; the fiber between the screens may be
fabricated from glass, ceramic plastic, or metal.
Foam blanket means the type of chemical
fume suppressant that generates a layer of foam across the surface
of a solution when current is applied to that solution.
Fresh water means water, such as tap
water, that has not been previously used in a process operation or,
if the water has been recycled from a process operation, it has been
treated and meets the effluent guidelines for chromium wastewater.
Hard chromium electroplating or industrial
chromium electroplating means a process by which a thick layer of
chromium (typically 1.3 to 760 microns) is electrodeposited on a
base material to provide a surface with functional properties such
as wear resistance, a low coefficient of friction, hardness, and
corrosion resistance. In this process, the part serves as the cathode
in the electrolytic cell and the solution serves as the electrolyte.
Hard chromium electroplating process is performed at current densities
typically ranging from 1,600 to 6,500 A/m2 for total plating
times ranging from 20 minutes to 36 hours depending upon the desired
plate thickness.
Hexavalent chromium means the form
of chromium in a valence state of +6.
Large, hard chromium electroplating facility means
a facility that performs hard chromium electroplating and has a maximum
cumulative potential rectifier capacity greater than or equal to
60 million amperehours per year (amphr/yr).
Maximum cumulative potential rectifier
capacity means the summation of the total installed rectifier
capacity associated with the hard chromium electroplating tanks
at a facility, expressed in amperes, multiplied by the maximum
potential operating schedule of 8,400 hours per year and 0.7,
which assumes that electrodes are energized 70 percent of
the total operating time. The maximum potential operating schedule
is based on operating 24 hours per day, 7 days per week, 50
weeks per year.
Operating parameter value means a
minimum or maximum value established for a control device or process
parameter which, if achieved by itself or in combination with one
or more other operating parameter values, determines that an owner
or operator is in continual compliance with the applicable emission
limitation or standard.
Packed-bed scrubber means an add-on
air pollution control device consisting of a single or double packed
bed that contains packing media on which the chromic acid droplets
impinge. The packed-bed section of the scrubber is followed by a
mist eliminator to remove any water entrained from the packed-bed
section.
Research or laboratory operation means
an operation whose primary purpose is for research and development
of new processes and products, that is conducted under the close
supervision of technically trained personnel, and that is not involved
in the manufacture of products for commercial sale in commerce, except
in a de minimis manner.
Small, hard chromium electroplating facility means
a facility that performs hard chromium electroplating and has a maximum
cumulative potential rectifier capacity less than 60 million
amphr/yr.
Stalagmometer means a device used
to measure the surface tension of a solution.
Surface tension means the property,
due to molecular forces, that exists in the surface film of all liquids
and tends to prevent liquid from spreading.
Tank operation means the time in which
current and/or voltage is being applied to a chromium electroplating
tank or a chromium anodizing tank.
Tensiometer means a device used to
measure the surface tension of a solution.
Trivalent chromium means the form
of chromium in a valence state of +3.
Trivalent chromium process means the
process used for electrodeposition of a thin layer of chromium onto
a base material using a trivalent chromium solution instead of a
chromic acid solution.
Wetting agent means the type of chemical
fume suppressant that reduces the surface tension of a liquid.
(b) Nomenclature. The nomenclature
used in this subpart has the following meaning:
(1) AMR = the allowable mass emission rate
from each type of affected source subject to the same emission limitation
in milligrams per hour (mg/hr).
(2) AMRsys = the allowable mass emission rate from affected sources
controlled by an add-on air pollution control device controlling emissions
from multiple sources in mg/hr.
(3) EL = the applicable emission limitation
from § 63.342 of this subpart in milligrams per dry standard
cubic meter (mg/dscm).
(4) IAtotal = the sum of all inlet
duct areas from both affected and nonaffected sources in meters squared.
(5) IDAi = the total inlet area
for all ducts associated with affected sources in meters squared.
(6) IDAi,a = the total inlet duct
area for all ducts conveying chromic acid from each type of affected
source performing the same operation, or each type of affected source
subject to the same emission limitation in meters squared.
(7) VR = the total of ventilation rates for
each type of affected source subject to the same emission limitation
in dry standard cubic meters per minute (dscm/min).
(8) VRinlet = the total ventilation
rate from all inlet ducts associated with affected sources in dscm/min.
(9) VRinlet,a = the total ventilation
rate from all inlet ducts conveying chromic acid from each type of
affected source performing the same operation, or each type of affected
source subject to the same emission limitation in dscm/min.
(10) VRtot = the average total
ventilation rate for the three test runs as determined at the outlet
by means of the Method 306 testing in dscm/min.
§ 63.342 Standards.
(a) Each owner or operator of an affected
source subject to the provisions of this subpart shall comply with
these requirements on and after the compliance dates specified in § 63.343(a)
of this subpart. All affected sources are regulated by applying maximum
achievable control technology.
(b) Applicability of emission limits.
(1) The emission limitations in this section
apply only during tank operation, and also apply during periods of
startup and shutdown as these are routine occurrences for affected
sources subject to this subpart. The emission limitations do not
apply during periods of malfunction, but the work practice standards
that address operation and maintenance and that are required by paragraph
(f) of this section must be followed during malfunctions.
(2) If an owner or operator is controlling
a group of tanks with a common addon air pollution control
device, the emission limitations of paragraphs (c), (d), and
(e) of this section apply whenever any one affected source is operated.
The emission limitation that applies to the group of affected sources
is:
(i) The emission limitation identified in
paragraphs (c), (d), and (e) of this section if the affected
sources are performing the same type of operation (e.g., hard
chromium electroplating), are subject to the same emission limitation,
and are not controlled by an addon air pollution control device
also controlling nonaffected sources;
(ii) The emission limitation calculated according
to § 63.344(e)(3) if affected sources are performing the
same type of operation, are subject to the same emission limitation,
and are controlled with an add-on air pollution control device that
is also controlling nonaffected sources; and
(iii) The emission limitation calculated according to § 63.344(e)(4)
if affected sources are performing different types of operations, or affected
sources are performing the same operations but subject to different emission
limitations, and are controlled with an add-on air pollution control device
that may also be controlling emissions from nonaffected sources.
(c)(1) Standards for hard chromium electroplating
tanks. During tank operation, each owner or operator of an
existing, new, or reconstructed affected source shall control chromium
emissions discharged to the atmosphere from that affected source
by not allowing the concentration of total chromium in the exhaust
gas stream discharged to the atmosphere to exceed:
(i) 0.015 milligrams of total chromium per
dry standard cubic meter (mg/dscm) of ventilation air (6.6 x 106 grains
per dry standard cubic foot [gr/dscf]); or
(ii) 0.03 mg/dscm (1.3 x 10-5 gr/dscf)
if the hard chromium electroplating tank is an existing affected
source and is located at a small, hard chromium electroplating facility.
(2)(i) An owner or operator may demonstrate
the size of a hard chromium electroplating facility through the definitions
in § 63.341(a) of this subpart. Alternatively, an owner
or operator of a facility with a maximum cumulative potential rectifier
capacity of 60 million amphr/yr or more may be considered
small if the actual cumulative rectifier capacity is less than 60
million amphr/yr as demonstrated using the following procedures:
(A) If records show that the facility's previous
annual actual rectifier capacity was less than 60 million amphr/yr,
by using nonresettable ampere-hr meters and keeping monthly records
of actual ampere-hr usage for each 12-month rolling period following
the compliance date in accordance with § 63.346(b)(12).
The actual cumulative rectifier capacity for the previous 12month
rolling period shall be tabulated monthly by adding the capacity
for the current month to the capacities for the previous 11 months;
or
(B) By accepting a Federallyenforceable
limit on the maximum cumulative potential rectifier capacity of a
hard chromium electroplating facility through the title V permit
required by § 63.340(e), and by maintaining monthly records
in accordance with § 63.346(b)(12) to demonstrate that
the limit has not been exceeded. The actual cumulative rectifier
capacity for the previous 12month rolling period shall be tabulated
monthly by adding the capacity for the current month to the capacities
for the previous 11 months.
(ii) Once the monthly records required to
be kept by § 63.346(b)(12) and by this paragraph show that
the actual cumulative rectifier capacity over the previous 12month
rolling period corresponds to the large designation, the owner or
operator is subject to the emission limitation identified in paragraph (c)(1)(i)
of this section, in accordance with the compliance schedule of § 63.343(a)(5).
(d) Standards for decorative chromium
electroplating tanks using a chromic acid bath and chromium anodizing
tanks. During tank operation, each owner or operator of an
existing, new, or reconstructed affected source shall control chromium
emissions discharged to the atmosphere from that affected source
by either:
(1) Not allowing the concentration of total
chromium in the exhaust gas stream discharged to the atmosphere to
exceed 0.01 mg/dscm (4.4 x 10-6 gr/dscf);
or
(2) If a chemical fume suppressant containing
a wetting agent is used, by not allowing the surface tension of the
electroplating or anodizing bath contained within the affected source
to exceed 45 dynes per centimeter (dynes/cm) (3.1 x 103 poundforce
per foot [lbf/ft]) at any time during operation of the
tank.
(e) Standards for decorative chromium
electroplating tanks using a trivalent chromium bath.
(1) Each owner or operator of an existing,
new, or reconstructed decorative chromium electroplating tank that
uses a trivalent chromium bath that incorporates a wetting agent
as a bath ingredient is subject to the recordkeeping and reporting
requirements of §§ 63.346(b)(14) and 63.347(i), but
are not subject to the work practice requirements of paragraph (f)
of this section, or the continuous compliance monitoring requirements
in § 63.343(c). The wetting agent must be an ingredient
in the trivalent chromium bath components purchased from vendors.
(2) Each owner or operator of an existing,
new, or reconstructed decorative chromium electroplating tank that
uses a trivalent chromium bath that does not incorporate a wetting
agent as a bath ingredient is subject to the standards of paragraph
(d) of this section.
(3) Each owner or operator of existing, new,
or reconstructed decorative chromium electroplating tank that had
been using a trivalent chromium bath that incorporates a wetting
agent and ceases using this type of bath must fulfill the reporting
requirements of § 63.347(i)(3) and comply with the applicable
emission limitation within the timeframe specified in § 63.343(a)(7).
(f) Work practice standards. The work
practice standards of this section address operation and maintenance
practices. All owners or operators subject to the standards in paragraphs
(c) and (d) of this section are subject to these work practice standards.
(1)(i) At all times, including periods of
startup, shutdown, and malfunction, owners or operators shall operate
and maintain any affected source, including associated air pollution
control devices and monitoring equipment, in a manner consistent
with good air pollution control practices, consistent with the operation
and maintenance plan required by paragraph (f)(3) of this section.
(ii) Malfunctions shall be corrected as soon
as practicable after their occurrence in accordance with the operation
and maintenance plan required by paragraph (f)(3) of this section.
(iii) Operation and maintenance requirements
established pursuant to section 112 of the Act are enforceable independent
of emissions limitations or other requirements in relevant standards.
(2)(i) Determination of whether acceptable
operation and maintenance procedures are being used will be based
on information available to the Administrator, which may include,
but is not limited to, monitoring results; review of the operation
and maintenance plan, procedures, and records; and inspection of
the source.
(ii) Based on the results of a determination
made under paragraph (f)(2)(i) of this section, the Administrator
may require that an owner or operator of an affected source make
changes to the operation and maintenance plan required by paragraph
(f)(3) of this section for that source. Revisions may be required
if the Administrator finds that the plan:
(A) Does not address a malfunction that has
occurred;
(B) Fails to provide for the operation of
the affected source, the air pollution control techniques, or the
control system and process monitoring equipment during a malfunction
in a manner consistent with good air pollution control practices;
or
(C) Does not provide adequate procedures
for correcting malfunctioning process equipment, air pollution control
techniques, or monitoring equipment as quickly as practicable.
(3) Operation and maintenance plan.
(i) The owner or operator of an affected
source subject to the work practices of paragraph (f) of this section
shall prepare an operation and maintenance plan to be implemented
no later than the compliance date. The plan shall be incorporated
by reference into the source's title V permit and shall include the
following elements:
(A) The plan shall specify the operation
and maintenance criteria for the affected source, the add-on air
pollution control device (if such a device is used to comply with
the emission limits), and the process and control system monitoring
equipment, and shall include a standardized checklist to document
the operation and maintenance of this equipment;
(B) For sources using an add-on air pollution
control device or monitoring equipment to comply with this subpart,
the plan shall incorporate the work practice standards for that device
or monitoring equipment, as identified in Table 2, if the specific
equipment used is identified in Table 2;
TABLE 2. SUMMARY OF WORK PRACTICE STANDARDS
Control technique
|
Work practice standards
|
Frequency
|
Composite mesh-pad (CMP) system
|
1. Visually inspect device to ensure
there is proper drainage, no chromic acid buildup on the pads,
and no evidence of chemical attack on the structural integrity
of the device.
|
1. 1/quarter
|
|
2. Visually inspect back portion
of the mesh pad closest to the fan to ensure there is no breakthrough
of chromic acid mist.
|
2. 1/quarter
|
|
3. Visually inspect ductwork from
tank or tanks to the control device to ensure there are no leaks.
|
3. 1/quarter
|
|
4. Perform washdown of the composite
mesh-pads in accordance with manufacturers recommendations.
|
4. Per manufacturer
|
Packed-bed scrubber (PBS)
|
1. Visually inspect device to ensure
there is proper drainage, no chromic acid buildup on the packed
beds, and no evidence of chemical attack on the structural integrity
of the device.
|
1. 1/quarter
|
|
2. Visually inspect back portion
of the chevron blade mist eliminator to ensure that it is dry and
there is no breakthrough of chromic acid mist.
|
2. 1/quarter
|
|
3. Same as number 3 above.
|
3. 1/quarter
|
|
4. Add fresh makeup water to the
top of the packed bed.a,b
|
4. Whenever makeup is added
|
PBS/CMP system
|
1. Same as for CMP system
2. Same as for CMP system
3. Same as for CMP system
4. Same as for CMP system
|
1. 1/quarter
2. 1/quarter
3. 1/quarter
4. Per manufacturer
|
Fiber-bed mist eliminatorc
|
1. Visually inspect fiber-bed unit
and prefiltering device to ensure there is proper drainage, no
chromic acid buildup in the units, and no evidence of chemical
attack on the structural integrity of the devices.
2. Visually inspect ductwork from tank or tanks to the control device to
ensure there are no leaks.
3. Perform washdown of fiber elements in accordance with manufacturers
recommendations.
|
1. 1/quarter
2. 1/quarter
3. Per manufacturer
|
Air pollution control device (APCD)
not listed in rule
|
To be proposed by the source for
approval by the Administrator
|
To be proposed by the source for
approval by the Administrator
|
Monitoring Equipment
|
|
|
Pitot tube
|
Backflush with water, or remove from
the duct and rinse with fresh water. Replace in the duct and rotate
180 degrees to ensure that the same zero reading is obtained. Check
pitot tube ends for damage. Replace pitot tube if cracked or fatigued.
|
1/quarter
|
Stalagmometer
|
Follow manufacturers recommendations.
|
|
aIf
greater than 50 percent of the scrubber water is drained (e.g.,
for maintenance purposes), makeup water may be added to the scrubber
basin.
bFor
horizontal-flow scrubbers, top is defined as the section of the
unit directly above the packing media such that the makeup water
would flow perpendicular to the air flow through the packing. For
vertical-flow units, the top is defined as the area downstream
of the packing material such that the makeup water would flow countercurrent
to the air flow through the unit.
cWork
practice standards for the control device installed upstream of
the fiber-bed mist eliminator to prevent plugging do not apply
as long as the work practice standards for the fiber-bed unit are
followed.
(C) If the specific equipment used is not
identified in Table 2, the plan shall incorporate proposed work
practice standards. These proposed work practice standards shall
be submitted to the Administrator for approval as part of the submittal
required under § 63.343(d).
(D) The plan shall specify procedures to
be followed to ensure that equipment or process malfunctions due
to poor maintenance or other preventable conditions do not occur;
and
(E) The plan shall include a systematic procedure
for identifying malfunctions of process equipment, add-on air pollution
control devices, and process and control system monitoring equipment
and for implementing corrective actions to address such malfunctions.
(ii) If the operation and maintenance plan
fails to address or inadequately addresses an event that meets the
characteristics of a malfunction at the time the plan is initially
developed, the owner or operator shall revise the operation and maintenance
plan within 45 days after such an event occurs. The revised plan
shall include procedures for operating and maintaining the process
equipment, add-on air pollution control device, or monitoring equipment
during similar malfunction events, and a program for corrective action
for such events.
(iii) Recordkeeping associated with the operation
and maintenance plan is identified in § 63.346(b). Reporting
associated with the operation and maintenance plan is identified
in § 63.347(g) and (h) and paragraph (f)(3)(iv) of this
section.
(iv) If actions taken by the owner or operator
during periods of malfunction are inconsistent with the procedures
specified in the operation and maintenance plan required by paragraph (f)(3)(i)
of this section, the owner or operator shall record the actions taken
for that event and shall report such actions within 2 working
days after commencing actions inconsistent with the plan. This report
shall be followed by a letter within 7 working days after the end
of the event, unless the owner or operator makes alternative reporting
arrangements, in advance, with the Administrator.
(v) The owner or operator shall keep the
written operation and maintenance plan on record after it is developed
to be made available for inspection, upon request, by the Administrator
for the life of the affected source or until the source is no longer
subject to the provisions of this subpart. In addition, if the operation
and maintenance plan is revised, the owner or operator shall keep
previous (i.e., superseded) versions of the operation and maintenance
plan on record to be made available for inspection, upon request,
by the Administrator for a period of 5 years after each revision
to the plan.
(vi) To satisfy the requirements of paragraph
(f)(3) of this section, the owner or operator may use applicable
standard operating procedure (SOP) manuals, Occupational Safety and
Health Administration (OSHA) plans, or other existing plans, provided
the alternative plans meet the requirements of this section.
(g) The standards in this section that apply
to chromic acid baths shall not be met by using a reducing agent
to change the form of chromium from hexavalent to trivalent.
§ 63.343 Compliance
provisions.
(a) Compliance dates.
(1) The owner or operator of an existing
affected source shall comply with the emission limitations in § 63.342
of this subpart as follows:
(i) No later than 1 year after the effective
date of this subpart if the affected source is a decorative chromium
electroplating tank; and
(ii) No later than 2 years after the effective
date of this subpart if the affected source is a hard chromium electroplating
tank or a chromium anodizing tank.
(2) The owner or operator of a new or reconstructed
affected source that has an initial startup after the effective date
of these standards shall comply immediately upon startup of the source.
The owner or operator of a new or reconstructed affected source that
has an initial startup after the proposal date of these standards
but before the effective date shall follow the compliance schedule
of § 63.6(b)(3) and (4) of subpart A.
(3) The owner or operator of an existing
area source that increases actual or potential emissions of hazardous
air pollutants such that the area source becomes a major source must
comply with the provisions for existing major sources, including
the reporting provisions of § 63.347(g), immediately upon
becoming a major source.
(4) The owner or operator of a new area source
(i.e., an area source for which construction or reconstruction
was commenced after December 16, 1993) that increases actual
or potential emissions of hazardous air pollutants such that the
area source becomes a major source must comply with the provisions
for new major sources, immediately upon becoming a major source.
(5) An owner or operator of an existing hard
chromium electroplating tank or tanks located at a small, hard chromium
electroplating facility that increases its maximum cumulative potential
rectifier capacity, or its actual cumulative rectifier capacity,
such that the facility becomes a large, hard chromium electroplating
facility must comply with the requirements of § 63.342(c)(1)(i)
for all hard chromium electroplating tanks at the facility no later
than 1 year after the month in which monthly records required by §§ 63.342(c)(2)
and 63.346(b)(12) show that the large designation is met.
(6) Request for an extension of compliance.
An owner or operator of an affected source or sources that requests
an extension of compliance shall do so in accordance with this paragraph
and the applicable paragraphs of § 63.6(i) of subpart A.
When the owner or operator is requesting the extension for more than
one affected source located at the facility, then only one request
may be submitted for all affected sources at the facility.
(i) The owner or operator of an existing
affected source who is unable to comply with a relevant standard
under this subpart may request that the Administrator (or a State,
when the State has an approved part 70 permit program and the source
is required to obtain a part 70 permit under that program, or a State,
when the State has been delegated the authority to implement and
enforce the emission standard for that source) grant an extension
allowing the owner or operator up to 1 additional year to comply
with the standard for the affected source. The owner or operator
of an affected source who has requested an extension of compliance
under this paragraph and is otherwise required to obtain a title
V permit for the source shall apply for such permit or apply to have
the title V permit revised to incorporate the conditions of the extension
of compliance. The conditions of an extension of compliance granted
under this paragraph will be incorporated into the owner or operator's
title V permit for the affected source(s) according to the provisions
of part 70 or Federal title V regulations in this chapter (42 U.S.C.
7661), whichever are applicable.
(ii) Any request under this paragraph for
an extension of compliance with a relevant standard shall be submitted
in writing to the appropriate authority not later than 6 months before
the affected source's compliance date as specified in this section.
(7) An owner or operator of a decorative
chromium electroplating tank that uses a trivalent chromium bath
that incorporates a wetting agent, and that ceases using the trivalent
chromium process, must comply with the emission limitation now applicable
to the tank within 1 year of switching bath operation.
(b) Methods to demonstrate initial compliance.
(1) Except as provided in paragraphs (b)(2)
and (b)(3) of this section, an owner or operator of an affected source
subject to the requirements of this subpart is required to conduct
an initial performance test as required under § 63.7, using
the procedures and test methods listed in § 63.7 and § 63.344.
(2) If the owner or operator of an affected
source meets all of the following criteria, an initial performance
test is not required to be conducted under this subpart:
(i) The affected source is a decorative chromium
electroplating tank or a chromium anodizing tank; and
(ii) A wetting agent is used in the plating
or anodizing bath to inhibit chromium emissions from the affected
source; and
(iii) The owner or operator complies with
the applicable surface tension limit of § 63.342(d)(2) as demonstrated
through the continuous compliance monitoring required by paragraph (c)(5)(ii)
of this section.
(3) If the affected source is a decorative
chromium electroplating tank using a trivalent chromium bath, and
the owner or operator is subject to the provisions of § 63.342(e),
an initial performance test is not required to be conducted under
this subpart.
(c) Monitoring to demonstrate continuous
compliance. The owner or operator of an affected source subject
to the emission limitations of this subpart shall conduct monitoring
according to the type of air pollution control technique that is
used to comply with the emission limitation. The monitoring required
to demonstrate continuous compliance with the emission limitations
is identified in this section for the air pollution control techniques
expected to be used by the owners or operators of affected sources.
(1) Composite mesh-pad systems.
(i) During the initial performance test,
the owner or operator of an affected source, or a group of affected
sources under common control, complying with the emission limitations
in § 63.342 through the use of a composite mesh-pad system
shall determine the outlet chromium concentration using the test
methods and procedures in § 63.344(c), and shall establish
as a site-specific operating parameter the pressure drop across the
system, setting the value that corresponds to compliance with the
applicable emission limitation, using the procedures in § 63.344(d)(5).
An owner or operator may conduct multiple performance tests to establish
a range of compliant pressure drop values, or may set as the compliant
value the average pressure drop measured over the three test runs
of one performance test and accept ± 1 inch of water
column from this value as the compliant range.
(ii) On and after the date on which the initial
performance test is required to be completed under § 63.7,
the owner or operator of an affected source, or group of affected
sources under common control, shall monitor and record the pressure
drop across the composite mesh-pad system once each day that any
affected source is operating. To be in compliance with the standards,
the composite meshpad system shall be operated within ± 1 inch
of water column of the pressure drop value established during the
initial performance test, or shall be operated within the range of
compliant values for pressure drop established during multiple performance
tests.
(2) Packed-bed scrubber systems.
(i) During the initial performance test,
the owner or operator of an affected source, or group of affected
sources under common control, complying with the emission limitations
in § 63.342 through the use of a packed-bed scrubber system
shall determine the outlet chromium concentration using the procedures
in § 63.344(c), and shall establish as site-specific operating
parameters the pressure drop across the system and the velocity pressure
at the common inlet of the control device, setting the value that
corresponds to compliance with the applicable emission limitation
using the procedures in § 63.344(d)(4) and (5). An owner
or operator may conduct multiple performance tests to establish a
range of compliant operating parameter values. Alternatively, the
owner or operator may set as the compliant value the average pressure
drop and inlet velocity pressure measured over the three test runs
of one performance test, and accept ± 1 inch of water
column from the pressure drop value and ± 10 percent
from the velocity pressure value as the compliant range.
(ii) On and after the date on which the initial
performance test is required to be completed under § 63.7,
the owner or operator of an affected source, or group of affected
sources under common control, shall monitor and record the velocity
pressure at the inlet to the packed-bed scrubber and the pressure
drop across the scrubber system once each day that any affected source
is operating. To be in compliance with the standards, the scrubber
system shall be operated within ± 10 percent of the
velocity pressure value established during the initial performance
test, and within ± 1 inch of water column of the pressure
drop value established during the initial performance test, or within
the range of compliant operating parameter values established during
multiple performance tests.
(3) Packed-bed scrubber/composite mesh-pad
system. The owner or operator of an affected source, or group
of affected sources under common control, that uses a packed-bed
scrubber in conjunction with a composite mesh-pad system to meet
the emission limitations of § 63.342 shall comply with
the monitoring requirements for composite mesh-pad systems as identified
in paragraph (c)(1) of this section.
(4) Fiber-bed mist eliminator.
(i) During the initial performance test,
the owner or operator of an affected source, or group of affected
sources under common control, complying with the emission limitations
in § 63.342 through the use of a fiber-bed mist eliminator
shall determine the outlet chromium concentration using the procedures
in § 63.344(c), and shall establish as a site-specific
operating parameter the pressure drop across the fiber-bed mist eliminator
and the pressure drop across the control device installed upstream
of the fiber bed to prevent plugging, setting the value that corresponds
to compliance with the applicable emission limitation using the procedures
in § 63.344(d)(5). An owner or operator may conduct multiple
performance tests to establish a range of compliant pressure drop
values, or may set as the compliant value the average pressure drop
measured over the three test runs of one performance test and accept ± 1 inch
of water column from this value as the compliant range.
(ii) On and after the date on which the initial
performance test is required to be completed under § 63.7,
the owner or operator of an affected source, or group of affected
sources under common control, shall monitor and record the pressure
drop across the fiber-bed mist eliminator, and the control device
installed upstream of the fiber bed to prevent plugging, once each
day that any affected source is operating. To be in compliance with
the standards, the fiber-bed mist eliminator and the upstream control
device shall be operated within ± 1 inch of water
column of the pressure drop value established during the initial
performance test, or shall be operated within the range of compliant
values for pressure drop established during multiple performance
tests.
(5) Wetting agent-type or combination
wetting agenttype/foam blanket fume suppressants.
(i) During the initial performance test,
the owner or operator of an affected source complying with the emission
limitations in § 63.342 through the use of a wetting agent
in the electroplating or anodizing bath shall determine the outlet
chromium concentration using the procedures in § 63.344(c).
The owner or operator shall establish as the site-specific operating
parameter the surface tension of the bath using Method 306B, appendix
A of this part, setting the maximum value that corresponds to compliance
with the applicable emission limitation. In lieu of establishing
the maximum surface tension during the performance test, the owner
or operator may accept 45 dynes/cm as the maximum surface tension
value that corresponds to compliance with the applicable emission
limitation. However, the owner or operator is exempt from conducting
a performance test only if the criteria of paragraph (b)(2)
of this section are met.
(ii) On and after the date on which the initial
performance test is required to be completed under § 63.7, the
owner or operator of an affected source shall monitor the surface
tension of the electroplating or anodizing bath. Operation of the
affected source at a surface tension greater than the value established
during the performance test, or greater than 45 dynes/cm if
the owner or operator is using this value in accordance with paragraph
(c)(5)(i) of this section, shall constitute noncompliance with the
standards. The surface tension shall be monitored according to the
following schedule:
(A) The surface tension shall be measured
once every 4 hours during operation of the tank with a stalagmometer
or a tensiometer as specified in Method 306B, appendix A
of this part.
(B) The time between monitoring can be increased
if there have been no exceedances. The surface tension shall be measured
once every 4 hours of tank operation for the first 40 hours
of tank operation after the compliance date. Once there are no exceedances
during 40 hours of tank operation, surface tension measurement
may be conducted once every 8 hours of tank operation. Once there
are no exceedances during 40 hours of tank operation, surface
tension measurement may be conducted once every 40 hours of tank
operation on an ongoing basis, until an exceedance occurs. The minimum
frequency of monitoring allowed by this subpart is once every 40
hours of tank operation.
(C) Once an exceedance occurs as indicated
through surface tension monitoring, the original monitoring schedule
of once every 4 hours must be resumed. A subsequent decrease in frequency
shall follow the schedule laid out in paragraph (c)(5)(ii)(B) of
this section. For example, if an owner or operator had been monitoring
an affected source once every 40 hours and an exceedance occurs,
subsequent monitoring would take place once every 4 hours of tank
operation. Once an exceedance does not occur for 40 hours of
tank operation, monitoring can occur once every 8 hours of tank operation.
Once an exceedance does not occur for 40 hours of tank operation
on this schedule, monitoring can occur once every 40 hours of tank
operation.
(iii) Once a bath solution is drained from
the affected tank and a new solution added, the original monitoring
schedule of once every 4 hours must be resumed, with a decrease in
monitoring frequency allowed following the procedures of paragraphs
(c)(5)(ii)(B) and (C) of this section.
(6) Foam blanket-type fume suppressants.
(i) During the initial performance test,
the owner or operator of an affected source complying with the emission
limitations in § 63.342 through the use of a foam blanket
in the electroplating or anodizing bath shall determine the outlet
chromium concentration using the procedures in § 63.344(c),
and shall establish as the site-specific operating parameter the
thickness of the foam blanket, setting the minimum thickness that
corresponds to compliance with the applicable emission limitation.
In lieu of establishing the minimum foam blanket thickness during
the performance test, the owner or operator may accept 2.54 centimeters
(1 inch) as the minimum foam blanket thickness that corresponds to
compliance with the applicable emission limitation. All foam blanket
measurements must be taken in close proximity to the workpiece or
cathode area in the plating tank(s).
(ii) On and after the date on which the initial
performance test is required to be completed under § 63.7,
the owner or operator of an affected source shall monitor the foam
blanket thickness of the electroplating or anodizing bath. Operation
of the affected source at a foam blanket thickness less than the
value established during the performance test, or less than 2.54 cm
(1 inch) if the owner or operator is using this value in accordance
with paragraph (c)(6)(i) of this section, shall constitute noncompliance
with the standards. The foam blanket thickness shall be measured
according to the following schedule:
(A) The foam blanket thickness shall be measured
once every 1 hour of tank operation.
(B) The time between monitoring can be increased
if there have been no exceedances. The foam blanket thickness shall
be measured once every hour of tank operation for the first 40 hours
of tank operation after the compliance date. Once there are no exceedances
for 40 hours of tank operation, foam blanket thickness measurement
may be conducted once every 4 hours of tank operation. Once there
are no exceedances during 40 hours of tank operation, foam blanket
thickness measurement may be conducted once every 8 hours of
tank operation on an ongoing basis, until an exceedance occurs. The
minimum frequency of monitoring allowed by this subpart is once per
8 hours of tank operation.
(C) Once an exceedance occurs as indicated
through foam blanket thickness monitoring, the original monitoring
schedule of once every hour must be resumed. A subsequent decrease
in frequency shall follow the schedule laid out in paragraph (c)(6)(ii)(B)
of this section. For example, if an owner or operator had been monitoring
an affected source once every 8 hours and an exceedance occurs, subsequent
monitoring would take place once every hour of tank operation. Once
an exceedance does not occur for 40 hours of tank operation,
monitoring can occur once every 4 hours of tank operation. Once an
exceedance does not occur for 40 hours of tank operation on
this schedule, monitoring can occur once every 8 hours of tank operation.
(iii) Once a bath solution is drained from
the affected tank and a new solution added, the original monitoring
schedule of once every hour must be resumed, with a decrease in monitoring
frequency allowed following the procedures of paragraphs (c)(6)(ii)(B)
and (C) of this section.
(7) Fume suppressant/add-on control device.
(i) If the owner or operator of an affected
source uses both a fume suppressant and add-on control device and
both are needed to comply with the applicable emission limit, monitoring
requirements as identified in paragraphs (c)(1) through (6)
of this section, and the work practice standards of Table 2, apply
for each of the control techniques used.
(ii) If the owner or operator of an affected
source uses both a fume suppressant and add-on control device, but
only one of these techniques is needed to comply with the applicable
emission limit, monitoring requirements as identified in paragraphs
(c)(1) through (6) of this section, and work practice standards of
Table 2, apply only for the control technique used to achieve compliance.
(8) Use of an alternative monitoring method.
(i) Requests and approvals of alternative
monitoring methods shall be considered in accordance with § 63.8(f)(1),
(f)(3), (f)(4), and (f)(5) of subpart A.
(ii) After receipt and consideration of an
application for an alternative monitoring method, the Administrator
may approve alternatives to any monitoring methods or procedures
of this subpart including, but not limited to, the following:
(A) Alternative monitoring requirements when
installation or use of monitoring devices specified in this subpart
would not provide accurate measurements due to interferences caused
by substances within the effluent gases; or
(B) Alternative locations for installing
monitoring devices when the owner or operator can demonstrate that
installation at alternate locations will enable accurate and representative
measurements.
(d) An owner or operator who uses an air
pollution control device not listed in this section shall submit
a description of the device, test results collected in accordance
with § 63.344(c) verifying the performance of the device
for reducing chromium emissions to the atmosphere to the level required
by this subpart, a copy of the operation and maintenance plan referenced
in § 63.342(f) including proposed work practice standards,
and appropriate operating parameters that will be monitored to establish
continuous compliance with the standards. The monitoring plan submitted
identifying the continuous compliance monitoring is subject to the
Administrator's approval.
§ 63.344 Performance
test requirements and test methods.
(a) Performance test requirements. Performance tests shall
be conducted using the test methods and procedures in this section
and § 63.7 of subpart A. Performance test results shall be
documented in complete test reports that contain the information required
by paragraphs (a)(1) through (a)(9) of this section. The test
plan to be followed shall be made available to the Administrator prior
to the testing, if requested.
(1) A brief process description;
(2) Sampling location description(s);
(3) A description of sampling and analytical
procedures and any modifications to standard procedures;
(4) Test results;
(5) Quality assurance procedures and results;
(6) Records of operating conditions during
the test, preparation of standards, and calibration procedures;
(7) Raw data sheets for field sampling and
field and laboratory analyses;
(8) Documentation of calculations; and
(9) Any other information required by the
test method.
(b)(1) If the owner or operator of an affected
source conducts performance testing at startup to obtain an operating
permit in the State in which the affected source is located, the
results of such testing may be used to demonstrate compliance with
this subpart if:
(i) The test methods and procedures identified
in paragraph (c) of this section were used during the performance
test;
(ii) The performance test was conducted under
representative operating conditions for the source;
(iii) The performance test report contains
the elements required by paragraph (a) of this section; and
(iv) The owner or operator of the affected
source for which the performance test was conducted has sufficient
data to establish the operating parameter value(s) that correspond
to compliance with the standards, as required for continuous compliance
monitoring under § 63.343(c) of this subpart.
(2) The results of tests conducted prior
to December 1991 in which Method 306A was used to demonstrate
the performance of a control technique are not acceptable.
(c) Test methods. Each owner or operator
subject to the provisions of this subpart and required by § 63.343(b)
to conduct an initial performance test shall use the test methods
identified in this section to demonstrate compliance with the standards
in § 63.342.
(1) Method 306 or Method 306A, "Determination
of Chromium Emissions from Decorative and Hard Chromium Electroplating
and Anodizing Operations" shall be used to determine the chromium
concentration from hard or decorative chromium electroplating tanks
or chromium anodizing tanks. The sampling time and sample volume
for each run of Methods 306 and 306A shall be at least 120 minutes
and 1.70 dscm (60 dscf), respectively. Methods 306 and
306A allow the measurement of either total chromium or hexavalent
chromium emissions. For the purposes of this standard, sources using
chromic acid baths can demonstrate compliance with the emission limits
of § 63.342 by measuring either total chromium or hexavalent
chromium. Hence, the hexavalent chromium concentration measured by
these methods is equal to the total chromium concentration for the
affected operations.
(2) The California Air Resources Board (CARB)
Method 425 may be used to determine the chromium concentration
from hard and decorative chromium electroplating tanks and chromium
anodizing tanks if the following conditions are met:
(i) If a colorimetric analysis method is
used, the sampling time and volume shall be sufficient to result
in 33 to 66 micrograms of catch in the sampling train.
(ii) If Atomic Absorption Graphite Furnace
(AAGF) or Ion Chromatography with a Post-column Reactor (ICPCR) analyses
were used, the sampling time and volume should be sufficient to result
in a sample catch that is 5 to 10 times the minimum detection limit
of the analytical method (i.e., 1.0 microgram per liter
of sample for AAGF and 0.5 microgram per liter of sample for
ICPCR).
(iii) In the case of either paragraph (c)(2)(i)
or (ii) of this section, a minimum of 3 separate runs must be conducted.
The other requirements of § 63.7 of subpart A that apply
to affected sources, as indicated in Table 1, must also be met.
(3) Method 306B, "Surface Tension Measurement
and Recordkeeping for Tanks used at Decorative Chromium Electroplating
and Anodizing Facilities," shall be used to measure the surface
tension of electroplating and anodizing baths.
(4) Alternate test methods may also be used
if the method has been validated using Method 301 and if approved
by the Administrator. Procedures for requesting and obtaining approval
are contained in § 63.7(f) of subpart A.
(d) Establishing site-specific operating
parameter values.
(1) Each owner or operator required to establish
site-specific operating parameters shall follow the procedures in
this section.
(2) All monitoring equipment shall be installed
such that representative measurements of emissions or process parameters
from the affected source are obtained. For monitoring equipment purchased
from a vendor, verification of the operational status of the monitoring
equipment shall include execution of the manufacturer's written specifications
or recommendations for installation, operation, and calibration of
the system.
(i) Specifications for differential pressure
measurement devices used to measure velocity pressure shall be in
accordance with Section 2.2 of Method 2 (40 CFR part 60,
appendix A).
(ii) Specification for differential pressure
measurement devices used to measure pressure drop across a control
system shall be in accordance with manufacturer's accuracy specifications.
(3) The surface tension of electroplating
and anodizing baths shall be measured using Method 306B, "Surface
Tension Measurement and Recordkeeping for Tanks used at Decorative
Chromium Electroplating and Anodizing Facilities." This method
should also be followed when wetting agent type or combination wetting
agent/foam blanket type fume suppressants are used to control chromium
emissions from a hard chromium electroplating tank and surface tension
measurement is conducted to demonstrate continuous compliance.
(4) The owner or operator of a source required
to measure the velocity pressure at the inlet to an add-on air pollution
control device in accordance with § 63.343(c)(2), shall
establish the sitespecific velocity pressure as follows:
(i) Locate a velocity traverse port in a
section of straight duct that connects the hooding on the plating
tank or tanks with the control device. The port shall be located
as close to the control system as possible, and shall be placed a
minimum of 2 duct diameters downstream and 0.5 diameter upstream
of any flow disturbance such as a bend, expansion, or contraction
(see Method 1, 40 CFR part 60, appendix A). If 2.5 diameters
of straight duct work does not exist, locate the port 0.8 of the
duct diameter downstream and 0.2 of the duct diameter upstream from
any flow disturbance.
(ii) A 12-point velocity traverse of the
duct to the control device shall be conducted along a single axis
according to Method 2 (40 CFR part 60, appendix A) using an S-type
pitot tube; measurement of the barometric pressure and duct temperature
at each traverse point is not required, but is suggested. Mark the
S-type pitot tube as specified in Method 1 (40 CFR part 60, appendix
A) with 12 points. Measure the velocity pressure (Dp) values for
the velocity points and record. Determine the square root of the
individual velocity point Dp values and average. The point with the
square root value that comes closest to the average square root value
is the point of average velocity. The Dp value measured for this
point during the performance test will be used as the reference for
future monitoring.
(5) The owner or operator of a source required
to measure the pressure drop across the add-on air pollution control
device in accordance with § 63.343(c)(1) through (4) may
establish the pressure drop in accordance with the following guidelines:
(i) Pressure taps shall be installed at any
of the following locations:
(A) At the inlet and outlet of the control
system. The inlet tap should be installed in the ductwork just prior
to the control device and the corresponding outlet pressure tap should
be installed on the outlet side of the control device prior to the
blower or on the downstream side of the blower;
(B) On each side of the packed bed within
the control system or on each side of each mesh pad within the control
system; or
(C) On the front side of the first mesh pad
and back side of the last mesh pad within the control system.
(ii) Pressure taps shall be sited at locations
that are:
(A) Free from pluggage as possible and away
from any flow disturbances such as cyclonic demisters.
(B) Situated such that no air infiltration
at measurement site will occur that could bias the measurement.
(iii) Pressure taps shall be constructed
of either polyethylene, polybutylene, or other nonreactive materials.
(iv) Nonreactive plastic tubing shall be
used to connect the pressure taps to the device used to measure pressure
drop.
(v) Any of the following pressure gauges
can be used to monitor pressure drop: a magnehelic gauge, an inclined
manometer, or a "U" tube manometer.
(vi) Prior to connecting any pressure lines
to the pressure gauge(s), each gauge should be zeroed. No calibration
of the pressure gauges is required.
(e) Special compliance provisions for
multiple sources controlled by a common add-on air pollution control
device.
(1) This section identifies procedures for
measuring the outlet chromium concentration from an add-on air pollution
control device that is used to control multiple sources that may
or may not include sources not affected by this subpart.
(2) When multiple affected sources performing
the same type of operation (e.g., all are performing hard chromium
electroplating), and subject to the same emission limitation, are
controlled with an add-on air pollution control device that is not
controlling emissions from any other type of affected operation or
from any nonaffected sources, the applicable emission limitation
identified in § 63.342 must be met at the outlet of the
add-on air pollution control device.
(3) When multiple affected sources performing
the same type of operation and subject to the same emission limitation
are controlled with a common add-on air pollution control device
that is also controlling emissions from sources not affected by these
standards, the following procedures should be followed to determine
compliance with the applicable emission limitation in § 63.342:
(i) Calculate the crosssectional area
of each inlet duct (i.e., uptakes from each hood) including
those not affected by the standard.
(ii) Determine the total sample time per
test run by dividing the total inlet area from all tanks connected
to the control system by the total inlet area for all ducts associated
with affected sources, and then multiply this number by 2 hours.
The calculated time is the minimum sample time required per test
run.
(iii) Perform Method 306 testing and
calculate an outlet mass emission rate.
(iv) Determine the total ventilation rate
from the affected sources by using equation 1:
Vrtot x (IDAi)/((sum)IAtotal)
= Vrinlet (1)
were VRtot is the average total ventilation
rate in dscm/min for the three test runs as determined at the outlet
by means of the Method 306 testing; IDAi is the total inlet
area for all ducts associated with affected sources; IAtotal is the
sum of all inlet duct areas from both affected and nonaffected sources;
and VRinlet is the total ventilation rate from all inlet ducts associated
with affected sources.
(v) Establish the allowable mass emission
rate of the system (AMRsys) in milligrams of total chromium per hour
(mg/hr) using equation 2:
(sum)VRinlet x EL x 60 minutes/hour = AMRsys
(2)
where (Sum)VRinlet is the total
ventilation rate in dscm/min from the affected sources, and EL is
the applicable emission limitation from § 63.342 in mg/dscm.
The allowable mass emission rate (AMRsys) calculated from
equation 2 should be equal to or less than the outlet three-run
average mass emission rate determined from Method 306 testing
in order for the source to be in compliance with the standard.
(4) When multiple affected sources performing
different types of operations (e.g., hard chromium electroplating,
decorative chromium electroplating, or chromium anodizing) are controlled
by a common add-on air pollution control device that may or may not
also be controlling emissions from sources not affected by these
standards, or if the affected sources controlled by the common add-on
air pollution control device perform the same operation but are subject
to different emission limitations (e.g., because one is a new hard
chromium plating tank and one is an existing small, hard chromium
plating tank), the following procedures should be followed to determine
compliance with the applicable emission limitation in § 63.342:
(i) Follow the steps outlined in paragraphs (e)(3)(i)
through (e)(3)(iii) of this section.
(ii) Determine the total ventilation rate
for each type of affected source using equation 3:
VRtot x (IDAi,a)/((sum)IAtotal)
= Vrinlet,a (3)
where VRtot is the average total
ventilation rate in dscm/min for the three test runs as determined
at the outlet by means of the Method 306 testing; IDAi,a is
the total inlet duct area for all ducts conveying chromic acid from
each type of affected source performing the same operation, or each
type of affected source subject to the same emission limitation;
IAtotal is the sum of all duct areas from both affected
and nonaffected sources; and VRinlet,a is the total ventilation
rate from all inlet ducts conveying chromic acid from each type of
affected source performing the same operation, or each type of affected
source subject to the same emission limitation.
(iii) Establish the allowable mass emission
rate in mg/hr for each type of affected source that is controlled
by the add-on air pollution control device using equation 4,
5, 6, or 7 as appropriate:
VRhc1 x ELhc1 x 60
minutes/hour = AMRhc1 (4)
VRhc2 x ELhc2 x 60 minutes/hour = AMRhc2 (5)
VRdc x ELdc x 60 minutes/hour = AMRdc (6)
VRca x ELca x 60 minutes/hour = AMRca (7)
where "hc" applies to the total of ventilation rates for all hard
chromium electroplating tanks subject to the same emission limitation, "dc" applies
to the total of ventilation rates for the decorative chromium electroplating
tanks, "ca" applies to the total of ventilation rates for the chromium
anodizing tanks, and EL is the applicable emission limitation from § 63.342
in mg/dscm. There are two equations for hard chromium electroplating tanks
because different emission limitations may apply (e.g., a new tank versus an
existing, small tank).
(iv) Establish the allowable mass emission
rate (AMR) in mg/hr for the system using equation 8, including each
type of affected source as appropriate:
AMRhc1 + AMRhc2 + AMRdc + AMRca =
AMRsys (8)
The allowable mass emission rate calculated from equation 8 should be
equal to or less than the outlet three-run average mass emission rate determined
from Method 306 testing in order for the source to be in compliance with
the standards.
(5) Each owner or operator that uses the
special compliance provisions of this paragraph to demonstrate compliance
with the emission limitations of § 63.342 shall submit
the measurements and calculations to support these compliance methods
with the notification of compliance status required by § 63.347(e).
(6) Each owner or operator that uses the
special compliance provisions of this section to demonstrate compliance
with the emission limitations of § 63.342 shall repeat
these procedures if a tank is added or removed from the control system
regardless of whether that tank is a nonaffected source. If the new
nonaffected tank replaces an existing nonaffected tank of the same
size and is connected to the control system through the same size
inlet duct then this procedure does not have to be repeated.
§ 63.345 Provisions
for new and reconstructed sources.
(a) This section identifies the preconstruction review requirements
for new and reconstructed affected sources that are subject to, or
become subject to, this subpart.
(b) New or reconstructed affected sources.
The owner or operator of a new or reconstructed affected source is
subject to § 63.5(a), (b)(1), (b)(5), (b)(6), and (f)(1)
of subpart A, as well as the provisions of this paragraph.
(1) After the effective date of these standards,
whether or not an approved permit program is effective in the State
in which an affected sources is (or would be) located, no person
may construct a new affected source or reconstruct an affected source
subject to this subpart, or reconstruct a source such that it becomes
an affected source subject to this subpart, without submitting a
notification of construction or reconstruction to the Administrator.
The notification shall contain the information identified in paragraphs
(b)(2) and (3) of this section, as appropriate.
(2) The notification of construction or reconstruction
required under paragraph (b)(1) of this section shall include:
(i) The owner or operator's name, title,
and address;
(ii) The address (i.e., physical location)
or proposed address of the affected source if different from the
owner's or operator's;
(iii) A notification of intention to construct
a new affected source or make any physical or operational changes
to an affected source that may meet or has been determined to meet
the criteria for a reconstruction as defined in § 63.2
of subpart A;
(iv) An identification of subpart N as the
basis for the notification;
(v) The expected commencement and completion
dates of the construction or reconstruction;
(vi) The anticipated date of (initial) startup
of the affected source;
(vii) The type of process operation to be
performed (hard or decorative chromium electroplating, or chromium
anodizing);
(viii) A description of the air pollution
control technique to be used to control emissions from the affected
source, such as preliminary design drawings and design capacity if
an add-on air pollution control device is used; and
(ix) An estimate of emissions from the source
based on engineering calculations and vendor information on control
device efficiency, expressed in units consistent with the emission
limits of this subpart. Calculations of emission estimates should
be in sufficient detail to permit assessment of the validity of the
calculations.
(3) If a reconstruction is to occur, the
notification required under paragraph (b)(1) of this section shall
include the following in addition to the information required in
paragraph (b)(2) of this section:
(i) A brief description of the affected source
and the components to be replaced;
(ii) A brief description of the present and
proposed emission control technique, including the information required
by paragraphs (b)(2)(viii) and (ix) of this section;
(iii) An estimate of the fixed capital cost
of the replacements and of constructing a comparable entirely new
source;
(iv) The estimated life of the affected source
after the replacements; and
(v) A discussion of any economic or technical
limitations the source may have in complying with relevant standards
or other requirements after the proposed replacements. The discussion
shall be sufficiently detailed to demonstrate to the Administrator's
satisfaction that the technical or economic limitations affect the
source's ability to comply with the relevant standard and how they
do so.
(vi) If in the notification of reconstruction,
the owner or operator designates the affected source as a reconstructed
source and declares that there are no economic or technical limitations
to prevent the source from complying with all relevant standards
or requirements, the owner or operator need not submit the information
required in paragraphs (b)(3)(iii) through (v) of this section.
(4) The owner or operator of a new or reconstructed
affected source that submits a notification in accordance with paragraphs
(b)(1) through (3) of this section is not subject to approval by
the Administrator. Construction or reconstruction is subject only
to notification and can begin upon submission of a complete notification.
(5) Submittal timeframes. After the
effective date of this subpart, whether or not an approved permit
program is effective in the State in which an affected source is
(or would be) located, an owner or operator of a new or reconstructed
affected source shall submit the notification of construction or
reconstruction required by paragraph (b)(1) of this section according
to the following schedule:
(i) If construction or reconstruction commences
after the effective date of this subpart, the notification shall
be submitted as soon as practicable before the construction or reconstruction
is planned to commence.
(ii) If the construction or reconstruction
had commenced and initial startup had not occurred before the effective
date of this subpart, the notification shall be submitted as soon
as practicable before startup but no later than 60 days after the
effective date of this subpart.
§ 63.346 Recordkeeping
requirements.
(a) The owner or operator of each affected
source subject to these standards shall fulfill all recordkeeping
requirements outlined in this section and in the General Provisions
to 40 CFR part 63, according to the applicability of subpart
A as identified in Table 1.
(b) The owner or operator of an affected
source subject to the provisions of this subpart shall maintain the
following records for such source:
(1) Inspection records for the add-on air
pollution control device, if such a device is used, and monitoring
equipment, to document that the inspection and maintenance required
by the work practice standards of § 63.342(f) and Table 2
have taken place. The record can take the form of a checklist and
should identify the device inspected, the date of inspection, a brief
description of the working condition of the device during the inspection,
and any actions taken to correct deficiencies found during the inspection.
(2) Records of all maintenance performed
on the affected source, the add-on air pollution control device,
and monitoring equipment;
(3) Records of the occurrence, duration,
and cause (if known) of each malfunction of process, add-on air pollution
control, and monitoring equipment;
(4) Records of actions taken during periods
of malfunction when such actions are inconsistent with the operation
and maintenance plan;
(5) Other records, which may take the form
of checklists, necessary to demonstrate consistency with the provisions
of the operation and maintenance plan required by § 63.342(f)(3);
(6) Test reports documenting results of all
performance tests;
(7) All measurements as may be necessary
to determine the conditions of performance tests, including measurements
necessary to determine compliance with the special compliance procedures
of § 63.344(e);
(8) Records of monitoring data required by § 63.343(c)
that are used to demonstrate compliance with the standard including
the date and time the data are collected;
(9) The specific identification (i.e., the
date and time of commencement and completion) of each period of excess
emissions, as indicated by monitoring data, that occurs during malfunction
of the process, add-on air pollution control, or monitoring equipment;
(10) The specific identification (i.e., the
date and time of commencement and completion) of each period of excess
emissions, as indicated by monitoring data, that occurs during periods
other than malfunction of the process, add-on air pollution control,
or monitoring equipment;
(11) The total process operating time of
the affected source during the reporting period;
(12) Records of the actual cumulative rectifier
capacity of hard chromium electroplating tanks at a facility expended
during each month of the reporting period, and the total capacity
expended to date for a reporting period, if the owner or operator
is using the actual cumulative rectifier capacity to determine facility
size in accordance with § 63.342(c)(2);
(13) For sources using fume suppressants
to comply with the standards, records of the date and time that fume
suppressants are added to the electroplating or anodizing bath;
(14) For sources complying with § 63.342(e),
records of the bath components purchased, with the wetting agent
clearly identified as a bath constituent contained in one of the
components;
(15) Any information demonstrating whether
a source is meeting the requirements for a waiver of recordkeeping
or reporting requirements, if the source has been granted a waiver
under § 63.10(f) of subpart A; and
(16) All documentation supporting the notifications
and reports required by § 63.9 and § 63.10 of
subpart A and § 63.347 of this subpart.
(c) All records shall be maintained for a
period of 5 years in accordance with § 63.10(b)(1)
of subpart A.
§ 63.347 Reporting
requirements.
(a) The owner or operator of each affected source subject to these
standards shall fulfill all reporting requirements outlined in this
section and in the General Provisions to 40 CFR part 63,
according to the applicability of subpart A as identified in Table
1. These reports shall be made to the Administrator at the appropriate
address as identified in § 63.13 of subpart A, or to the
delegated State authority.
(1) Reports required by subpart A and this
section may be sent by U.S. mail, fax, or by another courier.
(i) Submittals sent by U.S. mail shall be
postmarked on or before the specified date.
(ii) Submittals sent by other methods shall
be received by the Administrator on or before the specified date.
(2) If acceptable to both the Administrator
and the owner or operator of an affected source, reports may be submitted
on electronic media.
(b) The reporting requirements of this section
apply to the owner or operator of an affected source when such source
becomes subject to the provisions of this subpart.
(c) Initial notifications.
(1) The owner or operator of an affected
source that has an initial startup before the effective date of this
subpart shall notify the Administrator in writing that the source
is subject to this subpart. The notification shall be submitted no
later than 180 calendar days after the effective date of this subpart
and shall contain the following information:
(i) The name, title, and address of the owner
or operator;
(ii) The address (i.e., physical location)
of each affected source;
(iii) A statement that subpart N is the basis
for this notification;
(iv) Identification of the applicable emission
limitation and compliance date for each affected source;
(v) A brief description of each affected
source, including the type of process operation performed;
(vi) For sources performing hard chromium
electroplating, the maximum potential cumulative potential rectifier
capacity;
(vii) For sources performing hard chromium
electroplating, a statement of whether the affected source(s) is
located at a small or a large, hard chromium electroplating facility
and whether this will be demonstrated through actual or maximum potential
cumulative rectifier capacity;
(viii) For sources performing hard chromium
electroplating tanks, a statement of whether the owner or operator
of an affected source(s) will limit the maximum potential cumulative
rectifier capacity in accordance with § 63.342(c)(2) such
that the hard chromium electroplating facility is considered small;
and
(ix) A statement of whether the affected
source is located at a major source or an area source as defined
in § 63.2 of subpart A.
(2) The owner or operator of a new or reconstructed
affected source that has an initial startup after the effective date
of this standard shall submit an initial notification (in addition
to the notification of construction or reconstruction required by § 63.345(b)
of this subpart) as follows:
(i) A notification of the date when construction
or reconstruction was commenced, shall be submitted simultaneously
with the notification of